GIE asks Chile’s SEC to probe PMGD cap imposed after grid fault

The Chena–Cerro Navia outage triggered curbs, but GIE says the order does not explain which plants were selected or how the risk was assessed.

GIE asks Chile’s SEC to probe PMGD cap imposed after grid fault

Why it matters: The dispute tests how Chile’s grid operator can restrict distributed generation to manage a transmission risk—and what evidence must support the measure.

By the numbers:
  • 15% — maximum injection allowed for the affected plants, measured against installed capacity.

  • 85% — reduction from installed capacity under the restriction.

  • 220 kV — voltage of the Chena–Cerro Navia transmission facilities involved in the fault.

  • 75 milliseconds — approximate time taken to clear the disturbance.

The Association of Independent Energy Generators (GIE A.G.) has asked Chile’s Superintendence of Electricity and Fuels (SEC) to investigate the National Electric Coordinator’s (CEN) decision to cap output from a group of Small Distributed Generation Plants (PMGD) at 15% of installed capacity. The restriction followed a transmission fault on 8 November between the Chena and Cerro Navia substations in the Metropolitan Region.

GIE says the CEN’s communication did not explain how it set the limit, why particular plants were selected or how much the curtailment would reduce the identified risk. The association also says the order lacks defined review mechanisms and objective conditions for lifting the restriction. The SEC has not announced a decision or timetable for responding to the complaint.

The cap followed a fault on the Chena–Cerro Navia line

The disturbance occurred at about 14:55 on 220 kV transmission facilities and was cleared in approximately 75 milliseconds. It was associated with the disconnection of numerous distributed generation plants.

As a preventive measure, the CEN instructed the affected facilities from 10 November to limit injections to no more than 15% of installed capacity. The operator described the measure as temporary and subject to technical analysis. GIE acknowledges the CEN’s authority to take preventive steps to protect system security, but disputes whether the scale of the limit is proportionate. In the association’s view, the disconnection of a group of PMGDs during the event does not, by itself, justify a restriction of this magnitude.

GIE had asked the CEN to review and lift the measure on 17 November. Its complaint now asks the SEC to obtain the technical and operational records supporting the decision, including the fault reports and event data, and to require a reasoned reassessment if the restriction remains in place.

Complaint challenges application of Article 102

The filing also questions the application of Article 102 of Supreme Decree No. 88, as amended by Supreme Decree No. 1 of 2026. GIE says the rules provide for an economic-efficiency criterion when injections must be restricted. It wants the SEC to examine the procedures, calculations and supporting information used to determine the level of curtailment.

In preliminary analysis of the plant disconnections, GIE said they were mainly linked to the activation of vector-shift voltage anti-islanding (VVS) protections. These devices detect abrupt changes in electrical conditions to prevent a plant from continuing to operate while isolated from the grid. GIE maintains that the protection settings met regulatory requirements; that is the association’s assessment and does not, on its own, settle whether the CEN’s cap was justified.

The association asked for the restriction to be modified or lifted if the identified risk no longer exists or can be mitigated through less restrictive measures. The SEC’s review will determine whether the CEN must provide further technical grounds or reconsider the limit.